Fire alarm cables

Type: fire signal cable.
International symbol: AF (IEC 20-22, IEC 60332-3).
Rated voltage: 450 / 750V.
Field of use: indoors, for connecting appliances and devices used in fire signaling.
construction:
Conductor: twisted copper multifilament.
Insulation: on PVC bundles; aluminum foil cased with plastic; spare wire.
Sheath: red PVC, with flame retardancy.
Ambient temperature: -10 ° C to + 80 ° C.
PDF

Technical parameters:

Section External diameter Minimum radius of curvature Total mass/th>
(mm2) (mm) (mm) (kg/km)
2 x 0,75 5,30 53 45
4 x 0,75 6,80 68 68
2 x 1 7,20 72 63
4 x 1 8,20 82 96
2 x 1,5 8,10 81 80
4 x 1,5 9,10 91 135
2 x 2,5 9,30 93 120
4 x 2,5 11,40 114 200
Type: cable for fire signaling, with aluminum foil shielding, with flame propagation delay and without halogen release.
International symbol: JB (St) H Bd (VDE 0815).
Rated voltage: 450 / 750V.
Field of use: indoors, for connecting devices used in fire signaling.
construction:
Conductor: solid copper.
Insulation: on each bundle, without release of halogen (HI2); halogen-free foil; aluminum foil cased with special materials; spare wires.
Sheath: red in color, with a delay in the spread of the flame and without the release of halogen (without the release of toxic or corrosive gases), the bundles are twisted into four threads and they are twisted together.
Ambient temperature: posed: -30 ° C to + 70 ° C, moving: -5 ° C to +50 ° C.
Electrical properties at 20 ° C: conductor resistance: max. 73.2 Ohm / km, insulation resistance: min. 100 MOhm x km, maximum construction capacity: max. 120 nF / km, flattening the conductor at 800 Hz: kb. 1.2 dB / km, coupling capacity: max. 200 pF / 100 m.
PDF

Technical parameters:

Section Sheath thickness External diameter Copper mass Total mass
(mm) (mm) (mm) (kg/km) (kg/km)
1 x 2 x 0,8 1 6,5 11 60
2 x 2 x 0,8 1 6,7 21 77
4 x 2 x 0,8 1 9,9 41 123
6 x 2 x 0,8 1 10,4 62 152
10 x 2 x 0,8 1,2 12,8 103 220
16 x 2 x 0,8 1,4 18 164 290
20 x 2 x 0,8 1,4 19 203 350
24 x 2 x 0,8 1,4 19,3 243 405
30 x 2 x 0,8 1,4 20,1 304 495
40 x 2 x 0,8 1,4 21,2 404 635
50 x 2 x 0,8 1,6 24,9 505 788
60 x 2 x 0,8 1,6 27,2 606 1020
80 x 2 x 0,8 1,8 29,9 807 1270
100 x 2 x 0,8 2 35,7 1008 1520
Type: cable for fire signaling, with aluminum foil shielding, with flame propagation delay and without halogen release.
International symbol: JB (St) H Bd (VDE 0815).
Rated voltage: 450 / 750V.
Field of use: indoors, for connecting devices used in fire signaling. In places with fire risk, the insulation having a resistance to flame propagation of at least 180 minutes and the operation of the system for 30 minutes.
construction:
Conductor: solid copper, protection on mineral bundles.
Insulation: on each bundle, without release of halogen (HI2); halogen-free foil; aluminum foil cased with special materials; spare wires.
Sheath: red with flame retardant and no halogen release (HM2; no release of toxic or corrosive gases), the bundles are twisted into four threads and they are twisted together.
Ambient temperature: posed: -30 ° C to + 70 ° C, moving: -5 ° C to +50 ° C.
Electrical properties at 20 ° C: conductor resistance: max. 73.2 Ohm / km, insulation resistance: min. 100 MOhm x km, maximum construction capacity: max. 120 nF / km, flattening the conductor at 800 Hz: kb. 1.2 dB / km, coupling capacity: max. 200 pF / 100 m.
PDF

Technical parameters:

Section Sheath thickness External diameter Copper mass Total mass
(mm) (mm) (mm) (kg/km) (kg/km)
2 x 2 x 0,8 1 7,5 25 76
4 x 2 x 0,8 1 10,9 45 130
8 x 2 x 0,8 1,2 14,5 85 232
12 x 2 x 0,8 1,2 17,1 126 318
16 x 2 x 0,8 1,4 19,6 166 430
20 x 2 x 0,8 1,4 21,5 206 514
Type: cable for fire signaling, with or without aluminum foil shielding.
International symbol: -YY, JB-Y (St) Y (VDE 0815).
Rated voltage: 450 / 750V.
Field of use: indoors, for connecting devices used in fire signaling.
construction:
Conductor: solid copper (version without shielding YB-YY), insulation on each bundle of PVC.
Insulation: on each bundle with PVC; plastic foil; aluminum foil; spare wire;
Coat: made of red PVC, the bundles are twisted in pairs.
Ambient temperature: laid: -30 ° C to + 70 ° C, moving: -5 ° C to +50 ° C.
Electrical properties at 20 ° C: conductor resistance: max. 73.2 Ohm / km, insulation resistance: min. 100 MOhm x km, maximum construction capacity: max. 100 nF / km.
PDF

Technical parameters:

Section Sheath thickness External diameter Copper mass Total mass
(mm) (mm) (mm) (kg/km) (kg/km)
JB-YY        
2 x 0,8 1,1 4,8 10 35
3 x 0,8 1,1 5,2 15 44
4 x 0,8 1,1 5,5 20 51
JB-Y(St)Y        
1 x 2 x 0,8 1,1 5,7 11 41
2 x 2 x 0,8 1,1 6,4 21 60
4 x 2 x 0,8 1,1 9,5 41 100
5 x 2 x 0,8 1,1 9,8 52 123
6 x 2 x 0,8 1,1 10,7 62 145
10 x 2 x 0,8 1,3 13,2 103 220
12 x 2 x 0,8 1,3 14,3 123 255
20 x 2 x 0,8 1,3 17,1 203 390
30 x 2 x 0,8 1,5 20,4 304 570
40 x 2 x 0,8 1,5 23 404 730
50 x 2 x 0,8 1,7 26 505 920