Type: medium voltage copper cable, single phase, with PVC sheath.
International symbol: N2XSY (VDE 0276).
Rated voltage: 6/10 kV ... 20/36 kV.
Field of use: in electricity supply stations, in indoor spaces, in cable ducts, outdoors, in underground lines, in water, transformer stations, industrial areas for powering objectives. The screen limits the action of electromagnetic fields; the same effect is given by the semiconductor layers located at the level of the insulation.
construction:
Conductor: copper mutifilation, twisted and compacted, semiconductor layer no.1.
Insulation: made of cross-linked polyethylene, semiconductor layer no.2.
Shielding: copper wire, copper strip, separating layer.
Sheath: red PVC.
Ambient temperature: -5 ° C to +70 ° C.
PDF

Technical parameters:

Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XSY 6/10 kV          
1x50 RM/16 27,7 662 1187 220 234
1x70 RM/16 29,2 854 1413 269 292
1x95 RM/16 30,9 1094 1689 321 354
1x120 RM/16 32,3 1334 1952 364 407
1x150 RM/25 33,8 1723 2346 405 460
1x185 RM/25 35,4 2059 2707 457 527
1x240 RM/25 37,6 2587 3265 528 621
1x300 RM/25 39,8 3163 3870 593 709
1x400 RM/35 43,3 4234 4977 665 815
1x500 RM/35 46 5194 5956 739 921
Section External diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XSY 12/20 kV          
1x50 RM/16 31,9 662 1371 223 238
1x70 RM/16 33,4 854 1606 273 296
1x95 RM/16 35,1 1094 1893 325 358
1x120 RM/16 36,5 1334 2166 368 412
1x150 RM/25 38 1723 2566 410 466
1x185 RM/25 39,6 2059 2939 463 532
1x240 RM/25 41,8 2587 3510 543 627
1x300 RM/25 44 3163 4128 601 715
1x400 RM/35 47,5 4234 5255 674 819
1x500 RM/35 50,2 5194 6251 750 927
Section External diameter max. Copper mass total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
N2XSY 18/30 kV          
1x50 RM/16 36,9 662 1625 226 241
1x70 RM/16 38,4 854 1871 276 299
1x95 RM/16 40,1 1094 2170 329 362
1x120 RM/16 41,5 1334 2451 373 416
1x150 RM/25 43 1723 2865 415 469
1x185 RM/25 44,6 2059 3248 468 536
1x240 RM/25 46,8 2587 3834 541 630
1x300 RM/25 49 3163 4469 608 717
1x400 RM/35 52,7 4234 5618 684 823
1x500 RM/35 55,4 5194 6660 762 929
Section Wzternal diameter max. Copper mass Total mass Maximum ground load allowable Maximum air load allowable
(mm2) (mm) (kg/km) (kg/km) (A) (A)
2XSY 20/36 kV          
1x50 RM/16 38,5 662 1714 226 241
1x70 RM/16 40 584 1963 276 299
1x95 RM/16 41,7 1094 2267 329 362
1x120 RM/16 43,1 1334 2550 373 416
1x150 RM/25 44,6 1723 2967 415 469
1x185 RM/25 46,2 2059 3355 468 536
1x240 RM/25 48,4 2587 3947 541 630
1x300 RM/25 50,6 3163 4585 608 717
1x400 RM/35 54,3 4234 5767 684 823
1x500 RM/35 57,2 5194 6817 762 929