Type: aluminum cable with PVC sheath and copper shielding.
International symbol: NAYCWY (VDE 0276).
Rated voltage: 0.6 / 1 kV.
Field of use: in power plants, industrial halls or in other objectives where no additional mechanical protections are prescribed.
construction:
Conductor: made of single- or multi-wire aluminum.
Insulation: on PVC bundles.
Filling: PVC.
Protective sheath: PVC.
Shielding: made of copper wires.
Reinforcement: made of copper strips.
Sheath: black PVC, with increased delay in spreading fire.
Ambient temperature: -5 ° C to +70 ° C.
International symbol: NAYCWY (VDE 0276).
Rated voltage: 0.6 / 1 kV.
Field of use: in power plants, industrial halls or in other objectives where no additional mechanical protections are prescribed.
construction:
Conductor: made of single- or multi-wire aluminum.
Insulation: on PVC bundles.
Filling: PVC.
Protective sheath: PVC.
Shielding: made of copper wires.
Reinforcement: made of copper strips.
Sheath: black PVC, with increased delay in spreading fire.
Ambient temperature: -5 ° C to +70 ° C.
Technical parameters:
Section | External diameter min. | External diameter max. | Copper mass | Aluminum mass | Total mass | Maximum ground intensity allowable | Maximum air intensity allowable |
---|---|---|---|---|---|---|---|
(mm2) | (mm) | (mm) | (kg/km) | (kg/km) | (kg/km) | (A) | (A) |
4x16/10 | 23 | 27 | 68 | 186 | 865 | 76 | 63 |
4x25/10 | 27 | 34 | 68 | 290 | 1150 | 99 | 83 |
4x50/25 | 32 | 39 | 170 | 580 | 1690 | 142 | 124 |
4x95/35 | 41 | 48 | 240 | 1102 | 2790 | 211 | 190 |
4x150/50 | 49 | 56 | 340 | 1740 | 3970 | 270 | 252 |
4x240/50 | 59 | 66 | 340 | 2784 | 5670 | 308 | 289 |