Type: copper cable, PVC insulated and polyethylene outer sheath.
International symbol: E-XY2Y (VDE 0272).
Rated voltage: 0.6 / 1 kV.
Field of use: transport of energy indoors, outdoors, in the humid environment or in other places where it is not subject to mechanical damage.
construction:
Conductors: single- or multi-wire copper.
Insulation: on each bundle of PVC.
Filling: between bundles
Sheath: made of special polyethylene.
Ambient temperature: -5 ° C to +70 ° C.
PDF

Technical parameters:

Section External diamater min. External diameter max. Copper mass Total mass Maximum allowable ground intensity Maximum allowable air intensity
(mm2) (mm) (mm) (kg/km) (kg/km) (A) (A)
4x6 RE 16 20 240 540 56 43
4x10 RE 18 22 400 740 75 60
4x10 RM 18 22 400 740 75 60
4x16 RE 21 25 640 1030 98 80
4x16 RM 21 25 640 1030 98 80
4x25 RM 25 32 1000 1540 128 106