Type: OL-AL conductor with cross-linked polyethylene insulation, for 12/20 kV overhead power lines.
Internal symbol: OAC2X
International symbol: ACSR-XLPE (DIN 48204).
Standard: SF 2/1998, SFS 5791.
Field of use: For medium voltage electrical networks, where it is necessary to reduce the distance between the phases and where it is desired to eliminate the defects due to the accidental fall of vegetation on the networks.
construction:
Conductor pairs: aluminum wires, twisted concentrically around a galvanized steel core.
Insulation: black crosslinked polyethylene.
Technical data:
Minimum installation temperature: -20 ° C, maximum permissible conductor temperature: 90 ° C, rated voltage: 12/20 (24) kV, minimum installation radius: 15x cable diameter.
PDF

Technical parameters:

Section External diameter Insulation thickness Total mass Breaking resistance Resistance at 20 °C
(mm2) (mm) (mm) (kg/km) (kN) (Ohm/km)
Alum/Oţel Nom/max        
35/6 12,5/14,2 2.5 215 12.4 0.832
50/8 13,9/15,8 2.5 280 16.8 0.595
70/12 15,5/17,7 2.5 375 23.4 0.422
95/15 17,7/20,0 2.5 470 33.7 0.321
120/21 19,3/21,8 2.5 625 45.9 0.235
150/25 20,7/23,6 2.5 715 53.7 0.194